Abstract
This paper presents a fuzzy-logic-based protection scheme for detecting the direction of earth faults in a transmission network using polarized voltage. The IEEE 9-Bus transmission network has been used to test the fuzzy logic scheme in MATLAB/Simulink. The proposed scheme involves the measurement of RMS value of each phase voltage in order to detect occurrence of a fault; the direction of fault is determined by measuring the phase angle between the fault current and the polarized or reference voltage. The proposed scheme has been tested in six earth fault cases, faults in the forward and reverse direction per phase. The simulation results demonstrate that the proposed protection scheme is able to detect earth fault and classify the fault direction accurately within one cycle time.
Original language | English |
---|---|
Title of host publication | Proceedings - 2018 53rd International Universities Power Engineering Conference, UPEC 2018 |
Publisher | Institute of Electrical and Electronics Engineers Inc. |
ISBN (Electronic) | 9781538629109 |
DOIs | |
Publication status | Published - 20 Nov 2018 |
Event | IEEE 53rd International Universities Power Engineering Conference - Glasgow Caledonian University, Glasgow, Scotland, UK, Glasgow, United Kingdom Duration: 4 Sept 2018 → 7 Sept 2018 http://www.upec2018.com/ http://www.upec2018.com/ |